ESN
ESN Type 8591 Voltage Indicator Relay for 1500 V DC
Contact with us! 24 business hours (excluding weekends and holidays) to confirm stock status and estimated delivery time.
The type 8591 voltage indicator relay was developed especially for the recording and transmission
of voltage states from DC power supply units in railway operations. (No auxiliary power supply is needed to operate it.)
Technical data
Dimensions
see figure
Housing
Makrolon
Type of protection
IP 65
Protection class
Protection class II
Attachment
Screw fastening M4, see figure, by
means of an installation plate: Screw
fastening M8 or strip-type fastening
Installation plate
Dimensions
see figure
Material
Stainless steel 1.4571
Ambient temperature
-20°C to +70°C
Coil
Nominal DC voltage
1500 V (+20%/-30%)
Auxiliary power
none
Resistance
approx. 900 k ?
Inductivity (LI)
> 50 H
Power drawn
UN = 1500 V: approx. 2.5 W
UN = 1800 V: approx. 3.6 W
Udraw-in
900 V ± 10 %
Udrop-out
500 V ± 20%
Contact (reed contact)
1 changeover contact (zero-po-
tential)
2 changeover contact (zero-po-
tential)
Switching rating
max. 80 VA/60 W
Switching voltage
max. 250 V
Switching current
max. 1 A
Electric strength
15 kVe? (coil contact)
Coil connection
fixed connected and encapsulated
cable skeins
Cable
NSGAFöu (3 kV) 10mm2
Length
2 m
Configurations
Standard configuration
without installation plate
with installation plate
Large configuration
without installation plate
with installation plate
Double configuration
without installation plate
with installation plate
Ordering information
Type
Part No.
Voltage indicator relay,
type 8591/1500
Standard housing
- without installation
230300
plate, output 1 change-
over contact
- with installation plate,